Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2017, 07:45 AM
  • B 0844_B 0843_582017_004943.mp4

Date
05/08/2017
W/O
0624515
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00102
PipeID
P09137
Time
12:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO517
Sewer Name
B JOINT OUTFALL B - UNIT 7 RELIEF
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
26
Purpose
Routine Assessment
Project
20170505MDM_JOINT_OUTFALL_B_UNIT_7_RELIEF
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
B 0844
Downstream MH
B 0843
Dir. of Survey
Downstream
Length Surveyed
359.2 ft.
Total Length
359.2 ft.
Structural Index
3
Structural Quick
4121
Structural Rating
6
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole B 0844 to B 0843
MH: B 0844MH: B 0843downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM4 ft. H - Hole, from 04 to 05 o'clock, within 8 inches of joint: YES - CHIP75.2 ft. MGO - General Observation - 15" VCP184.5 ft. MWM - Water Mark, 70 %of cross sectional area349.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE359.2 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM

Observation photos (2)

  • Hole, from 04 to 05 o'clock, within 8 inches of joint: YES - CHIP

    4 ft. - Hole, from 04 to 05 o'clock, within 8 inches of joint: YES - CHIP

  • General Observation - 15" VCP

    75.2 ft. - General Observation - 15" VCP

Observations (8)

DistanceCodeObservation
4HCHIP
0MWM
0MWL
359.2AMH1:15AM
349.8FCHAIRLINE
75.2MGO15" VCP
184.5MWM
0AMH12:45AM

Properties (6)

custom_field_three
HOLE-SMALL CHIP OUT OF PIPE
custom_field_two
4
customer
LACSD
datetime
2017-05-08T00:45:59-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false