Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2017, 08:27 AM
  • 01 0648_01 0647_152017_025603.mp4

Date
01/05/2017
W/O
0607746
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00212
PipeID
P01147
Time
12:27 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0382
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20170103MDM_MOUNTAIN_VIEW_BELLE_VERNON_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 0647
Downstream MH
01 0648
Dir. of Survey
Upstream
Length Surveyed
350.5 ft.
Total Length
350.5 ft.
Structural Index
2
Structural Quick
4137
Structural Rating
55
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
55
Pipe schematic from manhole 01 0647 to 01 0648
MH: 01 0647MH: 01 0648upstream0 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM39.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open40.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H40.2 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H64 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H75.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open76.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL78.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open85.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL89 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL91 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open91.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H99.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT120.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H120.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open126.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open139.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open142.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL142.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H151.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H176.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped200.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open200.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL202.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL202.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL221.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped221.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL223.6 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H233 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE233.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open237.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open238.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL255.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL259.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL261.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL261.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Active267.4 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT315.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped342.4 ft. MGO - General Observation - 15" VCP347.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT350.5 ft. MWM - Water Mark, 20 %of cross sectional area350.5 ft. MWL - Water Level, 5 %of cross sectional area350.5 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM350.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active

Observation photos (3)

  • General Observation - 15" VCP

    8.1 ft. - General Observation - 15" VCP

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    111.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    250.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

Observations (44)

DistanceCodeObservation
199.1FLH
83.1FCSLIGHT
150.1TFOpen
211TFOpen
111.6FMSL
35.2TFCCapped
229.9FLH
275.3TFOpen
89TFActive
250.8FLSLIGHT
126.9FLH
259.4FLH
150.1FCSL
274.1FCSL
91.1FCSL
112.6TFOpen
129.4TFCCapped
272.3TFOpen
310.3FCH
350.5AMH3:35AM
3FCSLIGHT
229.8TFOpen
286.5FLH
261.5FCSL
0MWM
129.4FCSL
8.1MGO15" VCP
311.4TFOpen
310.3FLH
0MWL
224.1TFOpen
147.6FCSL
89.2FCSL
117.5FCHAIRLINE
117TFOpen
0AMH2:55AM
94.6FCSL
147.6FCSL
173.8TFCapped
259.5TFOpen
207.6FCSL
264.9FLSL
0MGOConn. @ Mh, 9 O' Clock. Active
207.6FCH

Properties (6)

custom_field_three
SLIGHT LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-01-05T00:27:32-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false