Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2017, 11:30 AM
  • 01 0653_01 0652_142017_033845.mp4

Date
01/04/2017
W/O
0607746
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00212
PipeID
P01153
Time
3:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0382
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20170103MDM_MOUNTAIN_VIEW_BELLE_VERNON_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
01 0653
Downstream MH
01 0652
Dir. of Survey
Downstream
Length Surveyed
283.7 ft.
Total Length
283.7 ft.
Structural Index
2
Structural Quick
3628
Structural Rating
34
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
39
Pipe schematic from manhole 01 0653 to 01 0652
MH: 01 0653MH: 01 0652downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM3.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT3.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE8.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL11.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL11.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - H13.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H23.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL27.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open28.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL29.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open31.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H39 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open39.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL41 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open42.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS42.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS42.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS42.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS66.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open68.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped108 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open110.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open118.1 ft. RTL - Roots Tap Lateral, from 03 to 05 o'clock, 10 %, within 8 inches of joint: YES118.1 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6" - Open-20% ROOTS141.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open143.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open180.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped185.2 ft. MGO - General Observation - 12" VCP193.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped226.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped229.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open245 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped283.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 25% HAIRLINE AT JOINTS283.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 25% SLIGHT AT JOINTS283.4 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 15% SLIGHT AT JOINTS283.4 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 20% AT JOINTS AT JOINTS283.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN283.7 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (1)

  • General Observation - 12" VCP

    185.2 ft. - General Observation - 12" VCP

Observations (41)

DistanceCodeObservation
3.2FCSLIGHT
0MWL
39TBOpen
11.1FCSL
245TFCapped
118.1RTL
283.4FC25% HAIRLINE AT JOINTS
8.5FCSL
31.7FLH
29.9TFOpen
283.4FC25% SLIGHT AT JOINTS
180.3TFCCapped
143.9TFOpen
110.2TFOpen
27.6TFOpen
283.4FL15% SLIGHT AT JOINTS
42.2FLSLIGHT AT JOINTS
3.2FCHAIRLINE
229.5TFOpen
283.4FL20% AT JOINTS AT JOINTS
193.1TFCCapped
11.1FLH
28.8FCSL
13.4FLH
39.8FLSL
0MWM
185.2MGO12" VCP
283.7AMH4:25AM
68.8TFCCapped
66.4TFOpen
41TBOpen
118.1TBDOpen-20% ROOTS
23.9FCSL
42.2FCSLIGHT AT JOINTS
0AMH3:30AM
283.5MGOConn. @ Mh, 9 O' Clock. OPEN
226.7TFCCapped
42.2FLHAIRLINE AT JOINTS
42.2FCHAIRLINE AT JOINTS
108TFOpen
141.5TFOpen

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-01-04T03:30:00-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false