Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 3, 2017, 08:38 AM
  • 01 0657_01 0656_132017_025205.mp4

Date
01/03/2017
W/O
0607746
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00212
PipeID
P01157
Time
12:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0375
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20170103MDM_MOUNTAIN_VIEW_BELLE_VERNON_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
01 0657
Downstream MH
01 0656
Dir. of Survey
Downstream
Length Surveyed
263.9 ft.
Total Length
263.9 ft.
Structural Index
2
Structural Quick
332B
Structural Rating
37
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
40
Pipe schematic from manhole 01 0657 to 01 0656
MH: 01 0657MH: 01 0656downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area6.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT6.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE9.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL12.4 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - H14.4 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL17 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL19.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL22 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL24.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL24.6 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL30.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL30.3 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL31.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open32.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL33.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open35 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS35 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS35 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS35 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS43.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open69.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open80.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open111.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open119.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open153.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open161 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% ROOTS161 ft. RFL - Roots Fine Lateral, from 01 to 03 o'clock - 8%192.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open202.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open231.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open254.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open263.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 30% SLIGHT AT JOINTS263.5 ft. FL - Fracture Longitudinal, at 08 TO 4o'clock, within 8 inches of joint: YES, Finish - 20% AT JOINTS HAIRLINE263.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 40% SLIGHT AT JOINTS263.5 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS263.9 ft. MSA - Survey Abandoned - SLIPPERY SURFACE WILL COMPLETE REVERSE INSPECTION

Observations (39)

DistanceCodeObservation
161TFDOpen-80% ROOTS
231.1TFOpen
22FCSL
6.3FCSLIGHT
0AMH2:25AM
0MWL
35FCSLIGHT AT JOINTS
263.5FC30% SLIGHT AT JOINTS
17FCSL
32.8FCSL
263.5FL20% AT JOINTS HAIRLINE
31.3TFOpen
69.7TFOpen
30.3FCSL
19.5FCSL
12.4FCH
35FLHAIRLINE AT JOINTS
161RFL8%
14.4FCSL
119.6TFOpen
263.9MSASLIPPERY SURFACE WILL COMPLETE REVERSE INSPECTION
263.5FC40% SLIGHT AT JOINTS
9.3FCSL
30.3FCSL
0MWM
33.5TFOpen
6.3FLHAIRLINE
43.7TFOpen
24.6FCSL
254.6TFOpen
111.7TFOpen
202.9TFOpen
192.1TFOpen
263.5FL20% SLIGHT AT JOINTS
24.6FCSL
35FLSLIGHT AT JOINTS
35FCHAIRLINE AT JOINTS
153.2TFOpen
80.2TFOpen

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-01-03T00:38:04-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false