Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2017, 08:46 PM
  • 19 0020_19 0019_462017_135939.mp4

Date
04/06/2017
W/O
0602259
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00727
PipeID
P15050
Time
1:46 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7379
Sewer Name
19 PALO VERDE TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
20170406DF_PALO_VERDE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
19 0019
Downstream MH
19 0020
Dir. of Survey
Upstream
Length Surveyed
98.5 ft.
Total Length
98.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 19 0019 to 19 0020
MH: 19 0019MH: 19 0020upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:13 PM0.5 ft. MGO - General Observation - ROACHES @ MH1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish23 ft. MGP - General Photograph - SPALLING96.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98.5 ft. MWL - Water Level, 20 %of cross sectional area98.5 ft. AMH - Downstream Manhole, Survey Begins - 1:55 PM98.5 ft. MGO - General Observation - ROACHES @ MH98.5 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - SPALLING

    75.5 ft. - General Photograph - SPALLING

Observations (9)

DistanceCodeObservation
2SSS
98.5AMH2:13 PM
0MWL
0AMH1:55 PM
0MGOROACHES @ MH
97.5SSS
0MWM
75.5MGPSPALLING
98MGOROACHES @ MH

Properties (4)

customer
LACSD
datetime
2017-04-06T13:46:39-07:00
documentation
FRANKLIN, BRAR, SHADLER
is_lateral_inspection
false