Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 10, 2018, 11:36 AM
  • 08 0507_08 0506_4102018_043843.mp4

Date
04/10/2018
W/O
0699099
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00564
Time
4:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0805
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20180406MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0505
Downstream MH
08 0504
Dir. of Survey
Downstream
Length Surveyed
151.6 ft.
Total Length
151.6 ft.
Structural Index
2
Structural Quick
4234
Structural Rating
42
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
42
Pipe schematic from manhole 08 0505 to 08 0504
MH: 08 0505MH: 08 0504downstream0 ft. MWL - Water Level, 5 %of cross sectional area - NO FLOW0 ft. AMH - Upstream Manhole, Survey Begins - 4:55AMAM0 ft. MWM - Water Mark, 5 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PIPE PEELING9.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped11.1 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H11.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE12.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8" - Capped14.2 ft. MGO - General Observation - 15" VCP24.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H24.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT28.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING PIPE70.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H79.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H79.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H95.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL99.1 ft. MMC - Material Change, Other (state in comments) - LINED PIPE101.7 ft. MGO - General Observation - TORN PIPE LINER START107.2 ft. MMC - Material Change, Other (state in comments) - LINED PIPE FINISH107.2 ft. MGO - General Observation - TORN PIPE LINER FINISH109.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped111.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT111.6 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SLIGHT116.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL121.2 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT122.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES - SL126.2 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - SL126.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL131.2 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL131.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H141 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H151.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped151.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped151.6 ft. AMH - Downstream Manhole, Survey Ends - 5:40AM

Observation photos (9)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PIPE PEELING

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PIPE PEELING

  • General Observation - 15" VCP

    14.2 ft. - General Observation - 15" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H

    70.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H

  • Material Change, Other (state in comments) - LINED PIPE

    99.1 ft. - Material Change, Other (state in comments) - LINED PIPE

  • General Observation - TORN PIPE LINER START

    101.7 ft. - General Observation - TORN PIPE LINER START

  • Material Change, Other (state in comments) - LINED PIPE FINISH

    107.2 ft. - Material Change, Other (state in comments) - LINED PIPE FINISH

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

    116.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    121.2 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES - SL

    122.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES - SL

Observations (34)

DistanceCodeObservation
79.8FCH
151.6AMH5:40AM
111.6FCSLIGHT
111.6FCSLIGHT
107.2MMCLINED PIPE FINISH
131.2FCSL
12.4TFCCapped
95.2FCSL
99.1MMCLINED PIPE
131.2FCH
28.5SSSPEELING PIPE
0MWLNO FLOW
109.6TFCCapped
14.2MGO15" VCP
126.2FMSL
141FCH
79.8FLH
122.1FMSL
24.1FCH
11.1FLH
0AMH4:55AMAM
126.2FLSL
24.1FCSLIGHT
121.2FMSLIGHT
107.2MGOTORN PIPE LINER FINISH
70.9FLH
151.1MGOConn. @ Mh, 9 O' Clock. Capped
0MWM
11.1FCHAIRLINE
2SSSPIPE PEELING
9.2TFCCapped
116.6FLSL
151.1MGOConn. @ Mh, 3 O' Clock. Capped
101.7MGOTORN PIPE LINER START

Properties (6)

custom_field_three
MULTIPLE SLIGHT JOINT TO JOINT-TORN LINER
custom_field_two
1
customer
LACSD
datetime
2018-04-10T04:36:48-07:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false