Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2018, 09:02 PM
  • C 0171_C 0170_3232018_142125.mp4

Date
03/23/2018
W/O
0697030
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00130
PipeID
P09695
Time
2:02 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7666
Sewer Name
C JOINT OUTFALL C - UNIT 5C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20180322DF_JOINT_OUTFALL_C_UNIT_5C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0171
Downstream MH
C 0170
Dir. of Survey
Downstream
Length Surveyed
331.2 ft.
Total Length
331.2 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole C 0171 to C 0170
MH: C 0171MH: C 0170downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:02 PM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG90.6 ft. MGP - General Photograph106.1 ft. MGP - General Photograph132.1 ft. MGO - General Observation - UNMARKED MH132.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active186.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES244 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start250.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish275 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES307 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES329.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.9 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG329.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.9 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish331.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active331.2 ft. AMH - Downstream Manhole, Survey Ends - 2:42 PM331.2 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. Active331.2 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach331.2 ft. MGO - General Observation - Grease Throughout The Reach (5%)

Observation photos (10)

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    90.6 ft. - General Photograph

  • General Photograph

    106.1 ft. - General Photograph

  • General Observation - UNMARKED MH

    132.1 ft. - General Observation - UNMARKED MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES

    186.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    244 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 02 to 05 o'clock,  , within 8 inches of joint: YES

    275 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    307 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
2SAP
329.9SAV
0MWL
2SAV
106.1MGP
331.2MGOConn. @ Mh, 3 O' Clock. Active
329.9SZ70% MAG
331.2AMH2:42 PM
329.9SSS
329.9SAP
275DAGS
331.2MGOConn. @ Mh, 5 O' Clock. Active
331.2MGOPeeling & Flaking Throughout The Reach
132.1MGOUNMARKED MH
307DAE
331.2MGOGrease Throughout The Reach (5%)
186.5DAGS
2SSS
2SZ70% MAG
132.1MGOConn. @ Mh, 9 O' Clock. Active
250.4SRV
244SRV
0AMH2:02 PM
0MWM
90.6MGP

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-03-23T14:02:26-07:00
documentation
FRANKLIN, BRAR
is_lateral_inspection
false