Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2018, 08:48 AM
  • 29 0337_29 0322_282018_013509.mp4

Date
02/08/2018
W/O
0688890
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01017
PipeID
P24356
Time
12:48 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0733
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20140208MDM_PACFIC_COAST_HIGHWAY_SEWER
Material
NRCP
Shape
Circular
Height
8 in.
Upstream MH
29 0337
Downstream MH
29 0322
Dir. of Survey
Downstream
Length Surveyed
321.6 ft.
Total Length
321.6 ft.
Structural Index
3
Structural Quick
4435
Structural Rating
39
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
49
Pipe schematic from manhole 29 0337 to 29 0322
MH: 29 0337MH: 29 0322downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT SMALL PEA AGG2 ft. SAM - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT8.6 ft. SAM - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES, - SLIGHT9 ft. SAM - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES - SLIGHT AGG10 ft. MGO - General Observation - 8" NRCP16.1 ft. SAM - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: NO - SLIGHT21.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SLIGHT VERY SMALL25.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active25.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT50.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open51 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - MODERATE AGG55.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT AGG55.4 ft. MGO - General Observation - 8" NRCP81.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-50% GREASE145.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-50% GREASE173.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% GREASE182.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SLIGHT AGG204.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active247.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% GREASE257.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open- 50% GREASE283.4 ft. FC - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES - SLIGHT285 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT320.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT321.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active-INCOMING321.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active-OUTGOING321.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT AGG321.2 ft. SAM - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES, Finish - SLIGHT AGG321.6 ft. AMH - Downstream Manhole, Survey Ends - 2;25AM

Observation photos (12)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT SMALL PEA AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT SMALL PEA AGG

  • Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    2 ft. - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES,  - SLIGHT

    8.6 ft. - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES, - SLIGHT

  • Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES - SLIGHT AGG

    9 ft. - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: YES - SLIGHT AGG

  • General Observation - 8" NRCP

    10 ft. - General Observation - 8" NRCP

  • Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: NO - SLIGHT

    16.1 ft. - Surface Aggregate Missing, from 04 to 08 o'clock, within 8 inches of joint: NO - SLIGHT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SLIGHT  VERY SMALL

    21.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SLIGHT VERY SMALL

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - MODERATE AGG

    51 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - MODERATE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT AGG

    55.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT AGG

  • General Observation - 8" NRCP

    55.4 ft. - General Observation - 8" NRCP

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% GREASE

    173.4 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% GREASE

  • Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

    283.4 ft. - Fracture Circumferential, from 07 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (32)

DistanceCodeObservation
21.8SAVSLIGHT VERY SMALL
10MGO8" NRCP
283.4FCSLIGHT
2SAVSLIGHT SMALL PEA AGG
81.3TFDOpen-50% GREASE
145.3TFDOpen-50% GREASE
247.5TFDOpen-80% GREASE
25.9FCSLIGHT
2SAMSLIGHT
173.4TFDOpen-80% GREASE
321.2MGOConn. @ Mh, 9 O' Clock. Active-INCOMING
51SAVMODERATE AGG
321.6AMH2;25AM
0MWL
0MWM
55.4SAVSLIGHT AGG
25.2TFActive
50.4TFOpen
16.1SAMSLIGHT
321.2MGOConn. @ Mh, 3 O' Clock. Active-OUTGOING
257.4TFDOpen- 50% GREASE
320.5FCSLIGHT
0MGOConn. @ Mh, 9 O' Clock. OPEN
204.2TFActive
182.4SAVSLIGHT AGG
321.2SAVSLIGHT AGG
55.4MGO8" NRCP
321.2SAMSLIGHT AGG
9SAMSLIGHT AGG
8.6SAMSLIGHT
285FCSLIGHT
0AMH1:40AM

Properties (6)

custom_field_three
MISSING SLIGHT AGG BOTTOM OF PIPE
custom_field_two
2
customer
LACSD
datetime
2018-02-08T00:48:00-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false