Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 10:41 AM
  • 03 0235_03 0234_25012018_025830.mp4

Date
01/25/2018
W/O
684824
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00385
PipeID
P04837
Time
2:41 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5421
Sewer Name
03 MARKET STREET TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
06
Purpose
Routine Assessment
Project
WO_684824_TV03122_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
03 0235
Downstream MH
03 0234
Dir. of Survey
Downstream
Length Surveyed
451.1 ft.
Total Length
451.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 03 0235 to 03 0234
MH: 03 0235MH: 03 0234downstream0 ft. AMH - Upstream Manhole, Survey Begins - 03 02350 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MWM - Water Mark, 25 %of cross sectional area5.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"41.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"78.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"111.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"148 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"184.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"209.2 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start221.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"245.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"278.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"332.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"377.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"403 ft. MGO - General Observation - Liner tape Unpeeling, Hanging at 12 oclock414.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"435.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish435.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"451.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK451.2 ft. AMH - Downstream Manhole, Survey Ends - 03 0234

Observation photos (1)

  • Deposits Settled Other,  15 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    209.2 ft. - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
41.7TF
221.7TF
332.1TF
451.2MGOCONNECTION AT MH 3 O'CLOCK
0.1MWM
451.2AMH03 0234
111.4TF
403MGOLiner tape Unpeeling, Hanging at 12 oclock
0AMH03 0235
435.1DSZ
209.2DSZ
148TF
184.7TF
0MWL
5.3TF
78.4TF
414.3TF
435.1TF
245.2TFA
278.8TF
377.6TF

Properties (8)

additional_info
SC347056
custom_field_two
4
customer
LACSD
datetime
2018-01-25T02:41:51-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
39082