Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2018, 11:21 AM
  • 03 0236_03 0235_25012018_033507.mp4

Date
01/25/2018
W/O
684824
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00385
PipeID
P04838
Time
3:21 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5421
Sewer Name
03 MARKET STREET TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
06
Purpose
Routine Assessment
Project
WO_684824_TV03122_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
03 0235
Downstream MH
03 0236
Dir. of Survey
Upstream
Length Surveyed
449.8 ft.
Total Length
449.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 03 0235 to 03 0236
MH: 03 0235MH: 03 0236upstream0 ft. MGO - General Observation - CONNECTION AT MH 5 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 03 02360.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK72.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"105.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"138.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"171.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"200.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"237.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"275.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"303.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"341.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"341.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES377.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"429.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"449.8 ft. AMH - Downstream Manhole, Survey Begins - 03 0235449.8 ft. MWL - Water Level, 15 %of cross sectional area449.8 ft. MWM - Water Mark, 25 %of cross sectional area

Observations (18)

DistanceCodeObservation
377.1TF
0AMH03 0235
108DAGS
19.9TF
449.7MGOCONNECTION AT MH 3 O'CLOCK
0MWL
212.7TF
72.2TF
174.7TF
344.3TF
449.8MGOCONNECTION AT MH 5 O'CLOCK
449.8AMH03 0236
311TF
248.9TF
0MWM
278TF
146.1TF
108.3TF

Properties (8)

additional_info
SC347056
custom_field_two
4
customer
LACSD
datetime
2018-01-25T03:21:21-08:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
39082