Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2017, 10:35 PM
  • 05 2272_05 2271 _01082018_230825.mp4

Date
12/18/2017
W/O
679437
Weather
Dry
Operator/Surveyor
S LOPEZ
Sewer ID
Z00429
PipeID
P07395
Time
2:35 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5368
Sewer Name
05 COLDEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_679437_TV05094_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 2272
Downstream MH
05 2271
Dir. of Survey
Downstream
Length Surveyed
244.3 ft.
Total Length
244.3 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
101
Pipe schematic from manhole 05 2272 to 05 2271
MH: 05 2272MH: 05 2271downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start0 ft. AMH - Upstream Manhole, Survey Begins - 05 22720 ft. MWM - Water Mark, 20 %of cross sectional area85 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start86 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES86 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES242 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish242 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish244.3 ft. AMH - Downstream Manhole, Survey Ends - 05 2271

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    85 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
244.3AMH05 2271
0MWL
86FL
242DAGS
85CM
86FL
242CM
0DAGS
0AMH05 2272
0MWM

Properties (7)

additional_info
SC346445
custom_field_two
2
customer
LACSD
datetime
2017-12-18T14:35:35-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
28956