Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2018, 06:58 PM
  • 29 0171_29 0170_9172018_121454.mp4

Date
09/17/2018
W/O
0726334
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00354
PipeID
P24067
Time
11:58 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7811
Sewer Name
29 28TH STREET TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180917DF_28TH_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
29 0170
Downstream MH
29 0171
Dir. of Survey
Upstream
Length Surveyed
166 ft.
Total Length
166 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 29 0170 to 29 0171
MH: 29 0170MH: 29 0171upstream0 ft. AMH - Upstream Manhole, Survey Ends - 12:38 PM0 ft. MGO - General Observation - Grease Throughout The Reach (5%)0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active1.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish1.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish16.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"20.7 ft. MGP - General Photograph62.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES71.4 ft. RTJ - Roots Tap Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR110.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"113.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"117.4 ft. MGP - General Photograph - GREASE140.5 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open142.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start144.7 ft. MGP - General Photograph147.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish150.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start159 ft. MGP - General Photograph164 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start164 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165.9 ft. MWM - Water Mark, 20 %of cross sectional area165.9 ft. MWL - Water Level, 15 %of cross sectional area166 ft. AMH - Downstream Manhole, Survey Begins - 12:04 PM

Observation photos (11)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    7 ft. - General Photograph

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    15.1 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish

    18.4 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish

  • General Photograph

    21.3 ft. - General Photograph

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

    23.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

  • General Photograph - GREASE

    48.6 ft. - General Photograph - GREASE

  • Roots Tap Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR

    94.6 ft. - Roots Tap Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    103.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • General Photograph

    145.3 ft. - General Photograph

Observations (24)

DistanceCodeObservation
94.6RTJ
145.3MGP
2SSS
15.1RFJ
149.9TFC
166AMH12:38 PM
7MGP
25.5TBOpen
103.4FL
164.4RFJ
18.4RFJ
0.1MWM
0AMH12:04 PM
21.3MGP
52.8TFC
55.2TFC
166MGOGrease Throughout The Reach (5%)
164.4CM
164.4SSS
0.1MWL
23.8RFJ
2CM
166MGOConn. @ Mh, 9 O' Clock. Active
48.6MGPGREASE

Properties (6)

additional_info
ON SCREEN TAPE NUMBER IS WRONG. CORRECT TAPE NUMBER IS G7811
custom_field_two
3
customer
LACSD
datetime
2018-09-17T11:58:22-07:00
documentation
FRANKLIN, VENDRYES, IGNACIO, PARAISO
is_lateral_inspection
false