Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 30, 2018, 09:00 AM
  • 15 1052_15 1051 _30042018_034658.mp4

Date
04/30/2018
W/O
696292
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00631
PipeID
P12811
Time
2:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5580
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_696292_TV15031_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1052
Downstream MH
15 1051
Dir. of Survey
Downstream
Length Surveyed
240.7 ft.
Total Length
240.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
2
Overall Quick
Overall Rating
96
Pipe schematic from manhole 15 1052 to 15 1051
MH: 15 1052MH: 15 1051downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1510520 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION IN MH 3 O'CLOCK0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start14 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"63 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"102.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"112.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"166.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"215.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"240.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish240.7 ft. AMH - Downstream Manhole, Survey Ends - 15 1051240.7 ft. MGO - General Observation - ACTIVE CONNECTION IN MH 3 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
102.2TBA
240.5DAGS
0AMH151052
215.6TFA
112.7TFC
0MWM
240.7AMH15 1051
240.7MGOACTIVE CONNECTION IN MH 3 O'CLOCK
0MWL
0MGOACTIVE CONNECTION IN MH 3 O'CLOCK
63TFA
0DAGS
14TFC
166.2TFA

Properties (6)

additional_info
SC358540
custom_field_two
3
customer
LACSD
datetime
2018-04-30T02:00:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false