Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2018, 07:49 AM
  • 15 1055_15 1054_01052018_010849.mp4

Date
05/01/2018
W/O
696292
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00631
PipeID
P12815
Time
12:49 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5581
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_696292_TV15031_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1054
Downstream MH
15 1055
Dir. of Survey
Upstream
Length Surveyed
323.6 ft.
Total Length
323.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412L
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
138
Pipe schematic from manhole 15 1054 to 15 1055
MH: 15 1054MH: 15 1055upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 10551.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish43.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"48.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"125 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"129.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"143.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"170 ft. TBC - Tap Break-In Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"175.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"216.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"226.4 ft. TBC - Tap Break-In Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"247.7 ft. MWM - Water Mark, 25 %of cross sectional area255.6 ft. MWL - Water Level, 20 %of cross sectional area292.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"321.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start323.6 ft. MWL - Water Level, 30 %of cross sectional area323.6 ft. MWM - Water Mark, 50 %of cross sectional area323.6 ft. AMH - Downstream Manhole, Survey Begins - 15 1054

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
107.3TBA
0MWL
280.3TFA
0MWM
194.3TFA
0AMH15 1054
2DAGS
30.9TFA
153.6TBC
275.2TFC
180.5TBA
97.2TBC
68MWL
148.1TBC
321.9DAGS
323.6AMH15 1055
198.6TFC
75.9MWM

Properties (6)

additional_info
SC358541
custom_field_two
3
customer
LACSD
datetime
2018-05-01T00:49:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false