Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2018, 05:06 AM
  • 15 1048_15 1047 _30042018_224706.mp4

Date
04/30/2018
W/O
696292
Weather
Dry
Operator/Surveyor
S.LOPEZ
Sewer ID
Z00631
PipeID
P12807
Time
10:06 PM
Certificate
U-111-1180
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5581
Sewer Name
15 SLACK ROAD TRUNK
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_696292_TV15031_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 1048
Downstream MH
15 1047
Dir. of Survey
Downstream
Length Surveyed
332.3 ft.
Total Length
332.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312M
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
142
Pipe schematic from manhole 15 1048 to 15 1047
MH: 15 1048MH: 15 1047downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 10480 ft. MGO - General Observation - ACTIVE CONNECTION 3 OCLOCK38.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"91.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"107.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS107.9 ft. RML - Roots Medium Lateral, from 02 to 06 o'clock, 25 %, within 8 inches of joint: YES128.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"172.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"176.7 ft. RFL - Roots Fine Lateral, from 08 to 10 o'clock176.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS225.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS234.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"278.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"283.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"323.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"328.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"332.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish332.3 ft. AMH - Downstream Manhole, Survey Ends - 15 1048332.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    107.9 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

  • Roots Medium Lateral, from 02 to 06 o'clock, 25 %, within 8 inches of joint: YES

    107.9 ft. - Roots Medium Lateral, from 02 to 06 o'clock, 25 %, within 8 inches of joint: YES

  • Roots Fine Lateral, from 08 to 10 o'clock

    176.7 ft. - Roots Fine Lateral, from 08 to 10 o'clock

Observations (23)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
332.3DAGS
128.3TFC
283.4TFA
0DAGS
107.9TFDROOTS
225.9TFDROOTS
323.8TFA
91.2TFA
176.7RFL
0MWM
176.7TFDROOTS
328.1TFA
332.3AMH15 1048
172.9TFC
0MWL
234.3TFA
38.9TFA
278.9TFC
107.9RML
0AMH15 1048
0MGOACTIVE CONNECTION 3 OCLOCK
332.3MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC358541
custom_field_two
3
customer
LACSD
datetime
2018-04-30T22:06:04-07:00
documentation
Pro Pipe
is_lateral_inspection
false