Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2018, 07:52 AM
  • 02 0993_02 2244 _04052018_005856.mp4

Date
05/04/2018
W/O
695978
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00279
PipeID
P03565
Time
12:52 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5609
Sewer Name
02 MONTEBELLO TRUNK
City
COMMERCE, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
WO_695978_TV02334_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0993
Downstream MH
02 2244
Dir. of Survey
Downstream
Length Surveyed
97.2 ft.
Total Length
97.2 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 0993 to 02 2244
MH: 02 0993MH: 02 2244downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 09930 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area6.4 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start62.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start62.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish96.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish97.2 ft. AMH - Downstream Manhole, Survey Ends - 02 2244

Observation photos (3)

  • Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

    6.4 ft. - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    62.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
62.5FM
0AMH02 0993
0MWM
0MWL
97.2AMH02 2244
6.4CM
96.9FM
62.5CM
9CM

Properties (6)

additional_info
SC359161
custom_field_two
3
customer
LACSD
datetime
2018-05-04T00:52:23-07:00
documentation
PRO-PIPE
is_lateral_inspection
false