Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2018, 07:56 AM
  • 01 0056_01 0055_03052018_013335.mp4

Date
05/03/2018
W/O
695951
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00725
Time
12:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5554
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_695951_TV01254_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0056
Downstream MH
01 0055
Dir. of Survey
Downstream
Length Surveyed
350.5 ft.
Total Length
350.5 ft.
Structural Index
3
Structural Quick
413M
Structural Rating
211
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
211
Pipe schematic from manhole 01 0056 to 01 0055
MH: 01 0056MH: 01 0055downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00560 ft. MWL - Water Level, 15 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start74.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"129 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"129.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.2 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES225.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"333.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"348.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350.5 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH350.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK350.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0055

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    191.2 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
0MGOCONNECTION AT MH 9 O'CLOCK
129.7TFC
129TFC
0MWM
3.1CM
348.3CM
225.2TFC
277.5TFC
77.6TFC
350.5MGOCAPPED LATERAL 9 O'CLOCK @ MH
333.3TFC
350.5MGOCONNECTION AT MH 3 O'CLOCK
74.6TFC
175.8TFC
329.2TFC
123.6TB
178.6TFC
0AMH01 0056
350.5AMH01 0055
227.5TFC
0MWL
191.2FM
279.6TFC

Properties (6)

additional_info
SC359309
custom_field_two
3
customer
LACSD
datetime
2018-05-03T00:56:51-07:00
documentation
PROPIPE
is_lateral_inspection
false