Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 11, 2018, 10:31 AM
  • 01 0983_01 0982_5112018_033327.mp4

Date
05/11/2018
W/O
0705547
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00228
PipeID
P01821
Time
3:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0853
Sewer Name
01 WRIGHT ROAD TRUNK
City
MAYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
02
Purpose
Routine Assessment
Project
20180511MDM_WRIGHT_ROAD_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
01 0983
Downstream MH
01 0982
Dir. of Survey
Downstream
Length Surveyed
225.8 ft.
Total Length
225.8 ft.
Structural Index
2
Structural Quick
342A
Structural Rating
36
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
36
Pipe schematic from manhole 01 0983 to 01 0982
MH: 01 0983MH: 01 0982downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:05AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN15.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE18.6 ft. FC - Fracture Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES - H34.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H39.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT45.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open47.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active54.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H62.6 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - H76 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H91.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H94 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H100.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped105.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open130.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H167.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H167.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H182.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H187.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H208.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H211.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H225.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active225.4 ft. MGO - General Observation - Conn. @ Mh, 4 O' Clock. Active225.8 ft. AMH - Downstream Manhole, Survey Ends - 4:30AM

Observation photos (1)

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped

    100.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped

Observations (27)

DistanceCodeObservation
94FCH
225.4MGOConn. @ Mh, 3 O' Clock. Active
208.7FLH
182.9FCH
167.2FLH
15.8FLHAIRLINE
0AMH4:05AM
0MWL
18.6FCH
45.4TFOpen
62.6FCH
211.2FCH
167.2FCH
76FCH
91.5FLH
187.9FCH
0MWM
225.4MGOConn. @ Mh, 4 O' Clock. Active
8TFOPEN
39.3FCSLIGHT
225.8AMH4:30AM
47.6TFActive
34.2FCH
130.4FCH
105.4TFOpen
100.6TFCCapped
54.6FCH

Properties (6)

custom_field_three
HAILINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2018-05-11T03:31:17-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false