Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 28, 2018, 06:41 PM
  • 18 0079_18 0078_8282018_115459.mp4

  • 18 0079_18 0078_8282018_121728.mp4

  • 18 0079_18 0078_8282018_121903.mp4

Date
08/28/2018
W/O
PENDING
Weather
Dry
Operator/Surveyor
KURT SHADLER
Sewer ID
Z00698
PipeID
P13897
Time
11:41 AM
Certificate
U-415-06024035
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7796
Sewer Name
18 SANTA FE STREET TRUNK
City
S. WHITTIER
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Maintenance Related
Project
20180827KS_SANTA_FE_STREET_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
18 0079
Downstream MH
18 0078
Dir. of Survey
Downstream
Length Surveyed
299 ft.
Total Length
299 ft.
Structural Index
2
Structural Quick
3222
Structural Rating
11
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 18 0079 to 18 0078
MH: 18 0079MH: 18 0078downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:44 A.M.0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"89.5 ft. MGP - General Photograph160.6 ft. CC - Crack Circumferential, from 07 to 04 o'clock, within 8 inches of joint: YES222.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish222.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish222.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start223.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start295.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish298 ft. VC - Vermin Cockroach, within 8 inches of joint: YES299 ft. AMH - Downstream Manhole, Survey Ends - 12:31 PM

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    89.5 ft. - General Photograph

  • Crack Circumferential, from 07 to 04 o'clock, within 8 inches of joint: YES

    160.6 ft. - Crack Circumferential, from 07 to 04 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
298VC
0MWL
222.1SAV
295.8SSS
160.6CC
222.7SSS
222.1SSS
0AMH11:44 A.M.
295.8SAV
11.8TFA
0MWL
2SAV
2SSS
223.9SAV
89.5MGP
299AMH12:31 PM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2018-08-28T11:41:09-07:00
documentation
SHADLER, FRANKLIN
is_lateral_inspection
false