Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2018, 10:51 AM
  • 05 1804A_05 1804 _20072018_035736.mp4

Date
07/20/2018
W/O
717852
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00466
PipeID
P07027
Time
3:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5756
Sewer Name
05 JANET LANE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Routine Assessment
Project
WO_717852_TV05329_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 1804A
Downstream MH
05 1804
Dir. of Survey
Downstream
Length Surveyed
87.3 ft.
Total Length
87.3 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
1
O&M Quick
4131
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
62
Pipe schematic from manhole 05 1804A to 05 1804
MH: 05 1804AMH: 05 1804downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 1804A0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK17.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.2 ft. TFI - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2"59.2 ft. RMC - Roots Medium Connection, from 07 to 10 o'clock, 20 %, within 8 inches of joint: YES81 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish87 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish87.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1804

Observation photos (4)

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    17.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

    59.2 ft. - Tap Factory Made Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 2"

  • Roots Medium Connection, from 07 to 10 o'clock, 20 %, within 8 inches of joint: YES

    59.2 ft. - Roots Medium Connection, from 07 to 10 o'clock, 20 %, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
81RFJ
87.3AMH05 1804
0MWL
0AMH05 1804A
0MWM
87CM
59.2TFI
59.2RMC
0MGOCONNECTION AT MH 9 O'CLOCK
17.2RFJ
18.4CM

Properties (6)

additional_info
SC359697
custom_field_two
3
customer
LACSD
datetime
2018-07-20T03:51:24-07:00
documentation
PROPIPE
is_lateral_inspection
false