Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2018, 05:54 AM
  • J 0014_J 0012 _19072018_233032.mp4

Date
07/19/2018
W/O
712432
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00060
PipeID
P11597
Time
10:54 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5784
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
WO_712432_TV08171_JUL2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0014
Downstream MH
J 0012
Dir. of Survey
Downstream
Length Surveyed
477.7 ft.
Total Length
477.7 ft.
Structural Index
4
Structural Quick
5H3R
Structural Rating
517
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
517
Pipe schematic from manhole J 0014 to J 0012
MH: J 0014MH: J 0012downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 001410.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start99.3 ft. SRP - Surface Reinforcement Projecting, at 02 o'clock, within 8 inches of joint: YES246 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish475 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK475 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK475 ft. AMH - Downstream Manhole, Survey Ends - J 0012477.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Projecting, at 02 o'clock, within 8 inches of joint: YES

    99.3 ft. - Surface Reinforcement Projecting, at 02 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
475MGOCONNECTION AT MH 9 O'CLOCK
475MGOCONNECTION AT MH 3 O'CLOCK
10.9SRV
475AMHJ 0012
477.7SAP
0MWM
99.3SRP
0MWL
10.9SAP
246SRV
0AMHJ 0014

Properties (6)

additional_info
SC359695
custom_field_two
1
customer
LACSD
datetime
2018-07-19T22:54:47-07:00
documentation
PROPIPE
is_lateral_inspection
false