Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 08:18 AM
  • B 0470C_B 0470A _08062018_012708.mp4

Date
06/08/2018
W/O
706863
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00094
PipeID
P08994
Time
1:18 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5691
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
07
Purpose
Routine Assessment
Project
WO_706863_TV16037_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 0470C
Downstream MH
B 0470A
Dir. of Survey
Downstream
Length Surveyed
167.5 ft.
Total Length
167.5 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
96
O&M Index
1
O&M Quick
1C00
O&M Rating
21
Overall Index
2
Overall Quick
Overall Rating
117
Pipe schematic from manhole B 0470C to B 0470A
MH: B 0470CMH: B 0470Adownstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 0470C5.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.3 ft. RFJ - Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YES35.6 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES63 ft. RFL - Roots Fine Lateral, at 03 o'clock63 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"66.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start129.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"154.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish167.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK167.5 ft. AMH - Downstream Manhole, Survey Ends - B 0470A167.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    66.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
167.5MGOCONNECTION AT MH 9 O'CLOCK
167.5AMHB 0470A
0MWL
5.3SAP
63RFL
35.6RFJ
63TF
0MWM
66.8RFJ
0AMHB 0470C
154.7RFJ
5.3RFJ
129.9TF
167.5SAP

Properties (6)

additional_info
SC359350
custom_field_two
3
customer
LACSD
datetime
2018-06-08T01:18:24-07:00
documentation
PROPIPE
is_lateral_inspection
false