Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 08:00 AM
  • B 0472_B 0471 _08062018_011203.mp4

Date
06/08/2018
W/O
706863
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00094
PipeID
P08996
Time
1:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5691
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
07
Purpose
Routine Assessment
Project
WO_706863_TV16037_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 0472
Downstream MH
B 0471
Dir. of Survey
Downstream
Length Surveyed
331 ft.
Total Length
331 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
201
O&M Index
1
O&M Quick
311L
O&M Rating
69
Overall Index
2
Overall Quick
Overall Rating
270
Pipe schematic from manhole B 0472 to B 0471
MH: B 0472MH: B 0471downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 04720 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area4.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"4.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start60 ft. RML - Roots Medium Lateral, at 12 o'clock, 25 %, within 8 inches of joint: NO60 ft. RFC - Roots Fine Connection, at 12 o'clock60 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"78.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"148.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"167.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"217.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"279.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"285.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start296.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish330.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331 ft. AMH - Downstream Manhole, Survey Ends - B 0471331 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    285.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0AMHB 0472
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
60RML
217.8TF
167.5TF
331AMHB 0471
60RFC
7.5RFJ
296.7FL
4.8TF
60TF
148.4TF
4.8SAP
285.5FL
330.9SAP
279.1TF
0MWM
331RFJ
78.5TF
0MWL

Properties (6)

additional_info
SC359350
custom_field_two
3
customer
LACSD
datetime
2018-06-08T01:00:05-07:00
documentation
PROPIPE
is_lateral_inspection
false