Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2018, 05:41 AM
  • H 0375_H 0342_09072018_231951.mp4

Date
07/09/2018
W/O
712466
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10804
Time
10:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5768
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
06
Purpose
Routine Assessment
Project
WO_712466_TV15225_JUL2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
H 0375
Downstream MH
H 0342
Dir. of Survey
Downstream
Length Surveyed
964.3 ft.
Total Length
964.3 ft.
Structural Index
3
Structural Quick
513e
Structural Rating
575
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
575
Pipe schematic from manhole H 0375 to H 0342
MH: H 0375MH: H 0342downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03750 ft. MWM - Water Mark, 35 %of cross sectional area4.3 ft. MGO - General Observation - MAG COAT14.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start919.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"958 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish958.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start958.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start964.3 ft. AMH - Downstream Manhole, Survey Ends - H 0342964.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish964.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    958 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    958.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    958.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
14.9SAV
964.3AMHH 0342
964.3SRV
919.2TF
958SAV
4.3MGOMAG COAT
0MWL
964.3SAP
958.1SRV
958.1SAP
0AMHH 0375
0MWM

Properties (7)

additional_info
SC359677
custom_field_two
2
customer
LACSD
datetime
2018-07-09T22:41:27-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
38626