Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 9, 2018, 09:02 AM
  • H 0869_H 0489A_09072018_022111.mp4

Date
07/09/2018
W/O
712094
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00181
PipeID
P20460
Time
2:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5766
Sewer Name
H JOINT OUTFALL H - UNIT 6
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
WO_712094_TV15212_JUL2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0869
Downstream MH
H 0489A
Dir. of Survey
Downstream
Length Surveyed
358 ft.
Total Length
358 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
204
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
204
Pipe schematic from manhole H 0869 to H 0489A
MH: H 0869MH: H 0489Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 08690 ft. MWM - Water Mark, 20 %of cross sectional area13.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start84.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"355.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish358 ft. AMH - Downstream Manhole, Survey Ends - H 0489A

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
84.5TF
13.8SAP
355.5SAP
0MWL
0AMHH 0869
358AMHH 0489A
0MWM

Properties (6)

additional_info
SC359675
custom_field_two
2
customer
LACSD
datetime
2018-07-09T02:02:13-07:00
documentation
PROPIPE
is_lateral_inspection
false