Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2018, 07:31 AM
  • G 0209_G 0208_12072018_004349.mp4

Date
07/12/2018
W/O
711942
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01180
PipeID
P25573
Time
12:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5773
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_711942_TV01122_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
G 0209
Downstream MH
G 0208
Dir. of Survey
Downstream
Length Surveyed
322.9 ft.
Total Length
322.9 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
188
Pipe schematic from manhole G 0209 to G 0208
MH: G 0209MH: G 0208downstream0 ft. AMH - Upstream Manhole, Survey Begins - G 02090 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES15.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES20.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start30 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"69.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"246 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"265.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"305 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"322.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK322.9 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish322.9 ft. AMH - Downstream Manhole, Survey Ends - G 0208

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    15.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    20.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
220.1TFC
265.6TFC
165.8TFC
117.9TFC
0AMHG 0209
322.9MGOCONNECTION AT MH 9 O'CLOCK
2.1DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
246TFC
305TFC
322.9CM
20.2CM
322.9AMHG 0208
15.4FL
69.5TFC
0MWL
30TF
0MWM

Properties (6)

additional_info
SC359682
custom_field_two
3
customer
LACSD
datetime
2018-07-12T00:31:06-07:00
documentation
PROPIPE
is_lateral_inspection
false