Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 01:36 PM
  • 05 1193_05 1192_7252018_072151.mp4

Date
07/25/2018
W/O
0717904
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00514
PipeID
P06433
Time
6:36 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7766
Sewer Name
05 ROSECRANS AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20180725SHO_ROSECRANS_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
7.5 in.
Upstream MH
05 1193
Downstream MH
05 1192
Dir. of Survey
Downstream
Length Surveyed
323 ft.
Total Length
323 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 1193 to 05 1192
MH: 05 1193MH: 05 1192downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 119311.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.8 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"157.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.8 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"261.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: NO, 6"323 ft. AMH - Downstream Manhole, Survey Ends - MH 1192

Observations (15)

DistanceCodeObservation
106.8TFD
145.1TF
213.9TFD
0MWL
0MWM
273.6TFD
323AMHMH 1192
261.6TFD
157.1TFD
210.8TFD
85.6TFD
0AMHMH 1193
53.1TFD
11.4TF
205.1TF

Properties (7)

custom_field_three
LINER IS IN GOOD CONDITION
custom_field_two
4
customer
LACSD
datetime
2018-07-25T06:36:21-07:00
documentation
OBREGON, BRAR, VENDRYES
is_lateral_inspection
false
lining
PVCP-Folded/Reformed