Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 15, 2021, 07:08 PM
  • A 0614_A 0613_01152021_111204.mp4

Date
01/15/2021
W/O
864944
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00316
PipeID
P07819
Time
11:08 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8379
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_864944_TV21041_DEC2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
A 0614
Downstream MH
A 0613
Dir. of Survey
Downstream
Length Surveyed
2.2 ft.
Total Length
2.2 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole A 0614 to A 0613
MH: A 0614MH: A 0613downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 06140 ft. MWM - Water Mark, 100 %of cross sectional area0 ft. MWL - Water Level, 100 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. LD - Alignment Down, 45 %2.2 ft. MSA - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observation photos (1)

  • Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

    2.2 ft. - Survey Abandoned - VIEW OF D/S SIPHON FROM U/S MH

Observations (6)

DistanceCodeObservation
2SSS
0AMHA 0614
2.1LD
2.2MSAVIEW OF D/S SIPHON FROM U/S MH
0MWM
0MWL

Properties (6)

custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-01-15T11:08:16-08:00
documentation
PRO PIPE
is_lateral_inspection
false