Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2018, 06:12 AM
  • 01 0053_01 0052A_01032018_232808.mp4

Date
03/01/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00721
Time
10:12 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5471
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0052A
Downstream MH
01 0053
Dir. of Survey
Upstream
Length Surveyed
150.4 ft.
Total Length
150.4 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
54
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
54
Pipe schematic from manhole 01 0052A to 01 0053
MH: 01 0052AMH: 01 0053upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 00535 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish57.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"60.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"96.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start115.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"118 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"150.4 ft. MWM - Water Mark, 10 %of cross sectional area150.4 ft. AMH - Downstream Manhole, Survey Begins - 01 0052A150.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK150.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE150.4 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    54 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
32.4TFC
0MWM
34.8TFC
54CM
145.4CM
0AMH01 0052A
0MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
89.9TFC
92.9TFC
150.4AMH01 0053
0MGOCOCKROACHES IN MANHOLE
0MWL

Properties (6)

additional_info
SC358477
custom_field_two
3
customer
LACSD
datetime
2018-03-01T22:12:56-08:00
documentation
PRO PIPE
is_lateral_inspection
false