Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2018, 10:09 AM
  • 01 0065_01 0064_02032018_032704.mp4

Date
03/02/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00734
Time
2:09 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5471
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0065
Downstream MH
01 0064
Dir. of Survey
Downstream
Length Surveyed
373.1 ft.
Total Length
373.1 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
219
O&M Index
2
O&M Quick
412N
O&M Rating
155
Overall Index
2
Overall Quick
Overall Rating
374
Pipe schematic from manhole 01 0065 to 01 0064
MH: 01 0065MH: 01 0064downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00650 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start75.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"77.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"129.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"132.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 4"193.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"196 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"213.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"235.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"247.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"274.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"313.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"316.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"355.8 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: NO355.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"358.7 ft. RFL - Roots Fine Lateral, from 01 to 03 o'clock358.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"371.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish371.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish373.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0064

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 12 o'clock,  , within 8 inches of joint: NO

    355.8 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: NO

  • Roots Fine Lateral, from 01 to 03 o'clock

    358.7 ft. - Roots Fine Lateral, from 01 to 03 o'clock

Observations (25)

DistanceCodeObservation
75.3TFC
247.5TFA
371.6CM
313.8TFA
132.1TFA
193.7TFA
235.6TFA
373.1AMH01 0064
0AMH01 0065
0MWL
358.7RFL
358.7TFA
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
129.3TFA
355.8DAE
77.7TFC
355.8TFA
371.6DAGS
196TFA
7.5CM
316.6TFA
2DAGS
213.7TFA
0MWM
274.4TFA

Properties (6)

additional_info
SC358477
custom_field_two
3
customer
LACSD
datetime
2018-03-02T02:09:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false