Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 6, 2018, 06:34 AM
  • 01 0075_01 0074_05032018_234406.mp4

Date
03/05/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00744
Time
10:34 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5473
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0075
Downstream MH
01 0074
Dir. of Survey
Downstream
Length Surveyed
175.1 ft.
Total Length
175.1 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
2
O&M Quick
412F
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
162
Pipe schematic from manhole 01 0075 to 01 0074
MH: 01 0075MH: 01 0074downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00750 ft. MWL - Water Level, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"78.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"123.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"170.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish173.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish175.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0074175.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE175.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOC

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    23 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
123.4TFC
0MGOCOCKROACHES IN MANHOLE
173.7DAGS
175.1AMH01 0074
39TFC
78.4TFA
175.1MGOCOCKROACHES IN MANHOLE
175.1MGOACTIVE CONNECTION AT MH 9 O'CLOC
0MWM
170.8CM
0AMH01 0075
0MWL
23CM
2DAGS

Properties (6)

additional_info
SC358479
custom_field_two
3
customer
LACSD
datetime
2018-03-05T22:34:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false