Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2018, 07:12 AM
  • 01 0048_01 0047A_01032018_002559.mp4

Date
02/28/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00712
Time
11:12 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5470
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0048
Downstream MH
01 0047A
Dir. of Survey
Downstream
Length Surveyed
27.4 ft.
Total Length
27.4 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 01 0048 to 01 0047A
MH: 01 0048MH: 01 0047Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 004812.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0047A27.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE27.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
12.1CM
27.4AMH01 0047A
0MWM
0AMH01 0048
27.4MGOCOCKROACHES IN MANHOLE
27.4MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
26CM

Properties (6)

additional_info
SC358476
custom_field_two
3
customer
LACSD
datetime
2018-02-28T23:12:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false