Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 5, 2018, 10:08 AM
  • 01 0085_01 0084_05032018_032615.mp4

Date
03/05/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00754
Time
2:08 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5472
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
FLORENCE-FIRESTONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0085
Downstream MH
01 0084
Dir. of Survey
Downstream
Length Surveyed
285.5 ft.
Total Length
285.5 ft.
Structural Index
3
Structural Quick
413I
Structural Rating
160
O&M Index
2
O&M Quick
412K
O&M Rating
122
Overall Index
3
Overall Quick
Overall Rating
282
Pipe schematic from manhole 01 0085 to 01 0084
MH: 01 0085MH: 01 0084downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00850 ft. MGO - General Observation - ACTIVE CONNECTION AT 9 O'CLOCK0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start10.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"104.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"138.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"146.6 ft. H - Hole, from 11 to 01 o'clock, within 8 inches of joint: NO157.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"194.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"194.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS242.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 4"246.2 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 4" - FRACTURE PRESENT, TAP MADE ACTIVE272.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0084285.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish285.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, from 11 to 01 o'clock, within 8 inches of joint: NO

    146.6 ft. - Hole, from 11 to 01 o'clock, within 8 inches of joint: NO

Observations (19)

DistanceCodeObservation
10.6CM
49.4TFC
0MWM
0AMH01 0085
104.4TFC
138.3TBA
194.6TFC
285.5AMH01 0084
272.9CM
2DAGS
285.5DAGS
146.6H
246.2TFDFRACTURE PRESENT, TAP MADE ACTIVE
0MGOACTIVE CONNECTION AT 9 O'CLOCK
285.5MGOCOCKROACHES IN MANHOLE
194.6DSZDEBRIS
242.6TFA
0MWL
157.5TFC

Properties (6)

additional_info
SC358478
custom_field_two
1
customer
LACSD
datetime
2018-03-05T02:08:41-08:00
documentation
PRO PIPE
is_lateral_inspection
false