Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2018, 07:56 AM
  • 01 0046_01 0045A_01032018_010802.mp4

Date
02/28/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P25564
Time
11:56 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5470
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0046
Downstream MH
01 0045A
Dir. of Survey
Downstream
Length Surveyed
165.1 ft.
Total Length
165.1 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 01 0046 to 01 0045A
MH: 01 0046MH: 01 0045Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 01 004613.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"49 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"92 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"94.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"141.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"143 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"163.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE163.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish164 ft. MGO - General Observation - ACTIVE CONNECTION @ 3 OC165.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0045A

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    13.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
143TFC
163.2MGOCOCKROACHES IN MANHOLE
13.7CM
46.7TFC
92TFC
165.1AMH01 0045A
141.2TFC
49TFC
163.2CM
94.9TFC
0MWM
164MGOACTIVE CONNECTION @ 3 OC
0MGOCOCKROACHES IN MANHOLE
0AMH01 0046

Properties (6)

additional_info
SC358476
custom_field_two
3
customer
LACSD
datetime
2018-02-28T23:56:42-08:00
documentation
PRO PIPE
is_lateral_inspection
false