Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2018, 07:53 AM
  • A 1114_A 1113_452018_012919.mp4

Date
04/05/2018
W/O
0697985
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00973
PipeID
P21044
Time
12:53 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0804
Sewer Name
A JOINT OUTFALL A - UNIT 9
City
PARAMOUNT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
35
Purpose
Capital Improvement Program Assesment
Project
20180405MDM_JOINT_OUTFALL_UNIT_9
Material
Vitrified Clay Pipe
Shape
Circular
Height
42 in.
Upstream MH
A 1114
Downstream MH
A 1113
Dir. of Survey
Downstream
Length Surveyed
50.6 ft.
Total Length
50.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole A 1114 to A 1113
MH: A 1114MH: A 1113downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MGO - General Observation - 42" VCP0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8 ft. MGO - General Observation - 42" VCP34.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT-JOINT TO JOINT -2' PIPE SECTION46.3 ft. MGO - General Observation - DROP MH-APPOX 1'50.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish50.6 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM

Observation photos (4)

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 42" VCP

    8 ft. - General Observation - 42" VCP

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT-JOINT TO JOINT -2' PIPE SECTION

    34.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT-JOINT TO JOINT -2' PIPE SECTION

  • General Observation - DROP MH-APPOX 1'

    46.3 ft. - General Observation - DROP MH-APPOX 1'

Observations (10)

DistanceCodeObservation
0AMH12:55AM
0MGO42" VCP
2DAGS
0MWL
0MWM
34.2FLSLIGHT-JOINT TO JOINT -2' PIPE SECTION
50.1DAGS
50.6AMH1:15AM
46.3MGODROP MH-APPOX 1'
8MGO42" VCP

Properties (7)

custom_field_three
SLIGHT FRACTURE JOINT TO JOINT
custom_field_two
2
customer
LACSD
datetime
2018-04-05T00:53:55-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false
year_laid
19950908