Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 3, 2018, 08:03 AM
  • 05 0641_05 0640_432018_011313.mp4

Date
04/03/2018
W/O
0697665
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00520
PipeID
P05866
Time
1:03 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0799
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
20180403MDM_SOUTH_INGLEWOOD_ORANGE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 0641
Downstream MH
05 0640
Dir. of Survey
Downstream
Length Surveyed
258.8 ft.
Total Length
258.8 ft.
Structural Index
2
Structural Quick
3A2B
Structural Rating
62
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
64
Pipe schematic from manhole 05 0641 to 05 0640
MH: 05 0641MH: 05 0640downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:10AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area8 ft. MGO - General Observation - 21" VCP11.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open16.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped19.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped20.6 ft. FS - Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE23.9 ft. FS - Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE23.9 ft. FS - Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT26.1 ft. MWM - Water Mark, 40 %of cross sectional area26.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO - SLIGHT34.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE54.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H54.7 ft. FS - Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES, Finish - SLIGHT54.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H59.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped62.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped62.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT64.3 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H64.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H73.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H75.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H77.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT77.8 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - H78.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - H85.3 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H107.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped110.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped125.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H149.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL149.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - S149.6 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H149.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H156 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H159.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H159.1 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H168.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped171.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped180 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H204.6 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H219.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H219.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H219.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL232.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped236 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped243.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL258.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped258.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active MIDDLE OF STACK258.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped258.8 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (7)

  • General Observation - 21" VCP

    8 ft. - General Observation - 21" VCP

  • Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    20.6 ft. - Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    23.9 ft. - Fracture Spiral, from 10 to 01 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO - SLIGHT

    26.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    62.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

    73.5 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

    75.3 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - H

Observations (51)

DistanceCodeObservation
168.7TFCCapped
156FLH
149.6FCSL
159.1FLH
107.7TBCCapped
77.8FLSLIGHT
125.2FCH
149.6FLS
258.4MGOConn. @ Mh, 3 O' Clock. Capped
16.3TFCCapped
232.9TFCCapped
64.3FCH
62.2TFCCapped
0AMH1:10AM
149.6FCH
78.3FLH
243.7FCSL
54.7FLH
73.5FLH
77.8FLH
23.9FSHAIRLINE
59.1TFCCapped
219.6FLH
149.6FCH
258.8AMH2:05AM
85.3FCH
23.9FSSLIGHT
204.6FCH
26.4FLSLIGHT
258.4MGOConn. @ Mh, 9 O' Clock. Active MIDDLE OF STACK
219.6FLH
8MGO21" VCP
159.1FCH
34.2FCHAIRLINE
62.2FLSLIGHT
54.7FSSLIGHT
75.3FLH
110.8TFCCapped
20.6FSHAIRLINE
171.9TFCCapped
0MWM
64.3FCH
236TFCCapped
26.1MWM
11.1TBOpen
258.4MGOConn. @ Mh, 9 O' Clock. Capped
180FLH
54.7FCH
19.1TFCCapped
0MWL
219.6FCSL

Properties (6)

custom_field_three
SLIGHTSPRIAL & LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2018-04-03T01:03:06-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false