Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2018, 11:21 AM
  • 15 0733_B 0650_422018_043916.mp4

Date
04/02/2018
W/O
0670896
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12932
Time
4:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0798
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
20180330MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0733
Downstream MH
B 0650
Dir. of Survey
Downstream
Length Surveyed
220.9 ft.
Total Length
220.9 ft.
Structural Index
3
Structural Quick
4222
Structural Rating
12
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
19
Pipe schematic from manhole 15 0733 to B 0650
MH: 15 0733MH: B 0650downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PELLING CONCRETE AGG ATTCHED2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG19.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped22.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active37.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped45.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open46.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 03 to 06 o'clock, , within 8 inches of joint: YES - PEELED CONCRETE AGG ATTCHED135.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped148.9 ft. MGO - General Observation - 15" NRCP148.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open212.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE MODERATE AGG ATTCHED220.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SLIGHT AGG220.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MOGERATE AGG220.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active LARGE INCOMING LINE220.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active220.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE AGG ATTCHED220.9 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PELLING CONCRETE AGG ATTCHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PELLING CONCRETE AGG ATTCHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG

  • Deposits Settled Other,  15 %of cross sectional area, from 03 to 06 o'clock,  , within 8 inches of joint: YES - PEELED CONCRETE AGG ATTCHED

    46.7 ft. - Deposits Settled Other, 15 %of cross sectional area, from 03 to 06 o'clock, , within 8 inches of joint: YES - PEELED CONCRETE AGG ATTCHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE MODERATE AGG ATTCHED

    212.3 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE MODERATE AGG ATTCHED

Observations (21)

DistanceCodeObservation
220.9AMH5:00AM
37.7TFCCapped
0MWL
220.5SAMSLIGHT AGG
0MWM
45.3TFOpen
22.6TFActive
220.5SAMMOGERATE AGG
212.3SSSPEELING CONCRETE MODERATE AGG ATTCHED
46.7DSZPEELED CONCRETE AGG ATTCHED
148.9MGO15" NRCP
0AMH4:30AM
220.5MGOConn. @ Mh, 9 O' Clock. Active LARGE INCOMING LINE
2SSSPELLING CONCRETE AGG ATTCHED
2SAMMODERATE AGG
220.5MGOConn. @ Mh, 9 O' Clock. Active
2SAMSLIGHT AGG
220.5SSSPEELING CONCRETE AGG ATTCHED
19.2TFCCapped
148.9TFOpen
135.8TFCCapped

Properties (6)

custom_field_three
PEELLING CONCRETE MODERATE AGG ATTCHED
custom_field_two
2
customer
LACSD
datetime
2018-04-02T04:21:52-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false