Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2018, 05:14 PM
  • Section#2_02 2090_02 2089__3292018__G6983.mp4

Date
03/29/2018
W/O
0695755
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00247
PipeID
P04406
Time
10:14 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6983
Sewer Name
02 DOUGLAS AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20180329DF_DOUGLAS_AVE_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
02 2090
Downstream MH
02 2089
Dir. of Survey
Downstream
Length Surveyed
117.6 ft.
Total Length
117.6 ft.
Structural Index
2
Structural Quick
5131
Structural Rating
60
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
62
Pipe schematic from manhole 02 2090 to 02 2089
MH: 02 2090MH: 02 2089downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:14 AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. B - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MGP - General Photograph4.9 ft. MGP - General Photograph - POSSIBLE PINCHED GASKET32.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - OPEN109.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - OPEN111.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES114.7 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Start117.6 ft. MSA - Survey Abandoned - HIGH WATER/DEBRIS/SAG117.6 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Finish117.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Broken, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph

    2 ft. - General Photograph

  • General Photograph - POSSIBLE PINCHED GASKET

    4.9 ft. - General Photograph - POSSIBLE PINCHED GASKET

  • Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - OPEN

    32.4 ft. - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - OPEN

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    111.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Water Level, Sag in pipe, 30 %of cross sectional area, Start

    114.7 ft. - Water Level, Sag in pipe, 30 %of cross sectional area, Start

  • Survey Abandoned - HIGH WATER/DEBRIS/SAG

    117.6 ft. - Survey Abandoned - HIGH WATER/DEBRIS/SAG

Observations (15)

DistanceCodeObservation
2SSS
117.6MSAHIGH WATER/DEBRIS/SAG
114.7MWLS
117.6MWLS
4.9MGPPOSSIBLE PINCHED GASKET
111.5DAGS
109.1TFOPEN
0AMH10:14 AM
0MWM
2B
0MWL
2CM
117.6SSS
2MGP
32.4TFOPEN

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2018-03-29T10:14:03-07:00
documentation
FRANKLIN, SHADLER
is_lateral_inspection
false