Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2018, 07:00 AM
  • 05 1603_05 1602_14032018_001437.mp4

Date
03/14/2018
W/O
690226
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00551
PipeID
P06827
Time
12:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5484
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
WO_690226_TV05176_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
05 1603
Downstream MH
05 1602
Dir. of Survey
Downstream
Length Surveyed
295.7 ft.
Total Length
295.7 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
147
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
265
Pipe schematic from manhole 05 1603 to 05 1602
MH: 05 1603MH: 05 1602downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 16030 ft. MWL - Water Level, 5 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 08 o'clock, , within 8 inches of joint: YES, Start52.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"105.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"155.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"212.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"245.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish267 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"295.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE295.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 08 o'clock, , within 8 inches of joint: YES, Finish295.7 ft. AMH - Downstream Manhole, Survey Ends - 05 1602

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2CM
267TBA
105.5TFA
295.7MGOCOCKROACHES IN MANHOLE
2.1DAGS
245.9CM
0AMH05 1603
0MWL
155.2TBA
295.7DAGS
295.7AMH05 1602
52.6TBA
212.6TBA

Properties (6)

additional_info
SC358490
custom_field_two
3
customer
LACSD
datetime
2018-03-14T00:00:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false