Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2018, 10:45 AM
  • 15 0778_15 0777_3292018_034928.mp4

Date
03/29/2018
W/O
0670896
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12979
Time
3:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0793
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
20180328MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0778
Downstream MH
15 0777
Dir. of Survey
Downstream
Length Surveyed
384.9 ft.
Total Length
384.9 ft.
Structural Index
3
Structural Quick
4331
Structural Rating
23
O&M Index
2
O&M Quick
3123
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
34
Pipe schematic from manhole 15 0778 to 15 0777
MH: 15 0778MH: 15 0777downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC8 ft. MGO - General Observation - 15" NRCP30.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open60.1 ft. SAM - Surface Aggregate Missing, from 09 to 11 o'clock, within 8 inches of joint: NO - MODERATE AGG63.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open91.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped100.6 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS100.6 ft. RML - Roots Medium Lateral, from 12 to 02 o'clock, 10 %, within 8 inches of joint: YES112.3 ft. SSS - Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - PELING CONCRETE SLIGHT AGG ATTCHED114.6 ft. RFJ - Roots Fine Joint, from 03 to 06 o'clock, within 8 inches of joint: YESR - 2%118.7 ft. SSS - Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MODERATE AGG ATTCHED124.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS152.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open172.2 ft. RFJ - Roots Fine Joint, from 03 to 06 o'clock, within 8 inches of joint: YESR - 2%203.5 ft. MWM - Water Mark, 40 %of cross sectional area233.2 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MODERATE AGG ATTCHED248 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE258.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open267.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 5" - Open-60% GREASE304 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped307.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open356.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN384.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN384.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SLIGHT384.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MODERATE AGG384.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE MODERATE AGG ATTCHED384.9 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (10)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

  • General Observation - 15" NRCP

    8 ft. - General Observation - 15" NRCP

  • Surface Aggregate Missing, from 09 to 11 o'clock, within 8 inches of joint: NO - MODERATE AGG

    60.1 ft. - Surface Aggregate Missing, from 09 to 11 o'clock, within 8 inches of joint: NO - MODERATE AGG

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS

    100.6 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS

  • Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - PELING CONCRETE SLIGHT AGG ATTCHED

    112.3 ft. - Surface Spalling, from 01 to 04 o'clock, within 8 inches of joint: NO - PELING CONCRETE SLIGHT AGG ATTCHED

  • Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MODERATE AGG ATTCHED

    118.7 ft. - Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MODERATE AGG ATTCHED

  • Water Mark, 40 %of cross sectional area

    203.5 ft. - Water Mark, 40 %of cross sectional area

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MODERATE AGG ATTCHED

    233.2 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MODERATE AGG ATTCHED

Observations (33)

DistanceCodeObservation
91.1TFCCapped
152.1TFOpen
304TFCCapped
2SSSPEELING CONCRETE
118.7SSSPEELING CONCRETE MODERATE AGG ATTCHED
233.2SSSPEELING CONCRETE MODERATE AGG ATTCHED
63.8TFOpen
384.6MGOConn. @ Mh, 3 O' Clock. OPEN
384.9AMH4:25AM
100.6TFDOpen-100% ROOTS
124.7TFDOpen-90% ROOTS
8MGO15" NRCP
114.6RFJ2%
0MWM
0MGOConn. @ Mh, 3 O' Clock. Active
172.2RFJ2%
248FLHAIRLINE
258.5TFOpen
307.2TFOpen
356.7TFOPEN
267.6TFDOpen-60% GREASE
112.3SSSPELING CONCRETE SLIGHT AGG ATTCHED
384.6SAMSLIGHT
30.9TFOpen
0MWL
2SAMSLIGHT AGG
100.6RML
384.6SAMMODERATE AGG
2SAMMODERATE AGG SPORATIC
384.6SSSPEELING CONCRETE MODERATE AGG ATTCHED
0AMH3:45AM
203.5MWM
60.1SAMMODERATE AGG

Properties (6)

custom_field_three
PEELING CONCRETE MODERATE AGG ATTCHED
custom_field_two
2
customer
LACSD
datetime
2018-03-29T03:45:00-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false