Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 28, 2018, 12:30 PM
  • 15 0779_15 0778_3282018_053637.mp4

Date
03/28/2018
W/O
0670896
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12980
Time
5:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0793
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
20180328MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0779
Downstream MH
15 0778
Dir. of Survey
Downstream
Length Surveyed
197.8 ft.
Total Length
197.8 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 15 0779 to 15 0778
MH: 15 0779MH: 15 0778downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 5:30AM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC19.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MADERATE AGG ATTTCHED77 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% ROOTS103.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open118.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped122.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active161.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open164.9 ft. MGO - General Observation - 15" NRCP197.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETYE MODERATE AGG ATTCHED197.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT AGG197.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MODERATE AGG SPORATIC197.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active197.8 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MADERATE AGG ATTTCHED

    19.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE MADERATE AGG ATTTCHED

  • General Observation - 15" NRCP

    164.9 ft. - General Observation - 15" NRCP

Observations (20)

DistanceCodeObservation
197.8AMH5:50AM
103.8TFOpen
0MWL
164.9MGO15" NRCP
118.9TFCCapped
0MGOConn. @ Mh, 9 O' Clock. OPEN
77TFDOpen-80% ROOTS
122.1TBActive
0MGOConn. @ Mh, 3 O' Clock. Active
2SAVSLIGHT AGG
197.2SSSPEELING CONCRETYE MODERATE AGG ATTCHED
0AMH5:30AM
2SSSPEELING CONCRETE
19.7SSSPEELING CONCRETE MADERATE AGG ATTTCHED
197.2SAVSLIGHT AGG
2SAVMODERATE AGG SPORATIC
0MWM
197.2SAVMODERATE AGG SPORATIC
161.3TFOpen
197.2MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

custom_field_three
PEELING CONCRETE MODERATE AGG ATTCHED
custom_field_two
2
customer
LACSD
datetime
2018-03-28T05:30:00-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false