Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 28, 2018, 09:07 AM
  • 15 0789_15 0788_3282018_021605.mp4

Date
03/28/2018
W/O
0670896
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12990
Time
2:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0792
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
20180328MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0789
Downstream MH
15 0788
Dir. of Survey
Downstream
Length Surveyed
328.6 ft.
Total Length
328.6 ft.
Structural Index
3
Structural Quick
3721
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole 15 0789 to 15 0788
MH: 15 0789MH: 15 0788downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE2 ft. MGO - General Observation - MAG COAT 30% START 8:00 TO 4:007 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped8 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC8 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG UNDER MAG COAT19 ft. MGO - General Observation - MAG COAT 80% START24.4 ft. SAV - Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - MODERATE AGG SPORATIC42.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG42.7 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SLIGHT AGG42.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC69.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC69.3 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - MODERATE AGG SPORATIC69.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish90.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open108.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC225.5 ft. MGO - General Observation - MAG COAT 70% START319.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open328.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC328.1 ft. MGO - General Observation - MAG COAT 70% FINISH328.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MADERATE AGG SPORATIC328.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE328.6 ft. AMH - Downstream Manhole, Survey Ends - 2:40AM

Observation photos (10)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE

  • General Observation - MAG COAT 30% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 30% START 8:00 TO 4:00

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

    8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG UNDER MAG COAT

    8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SLIGHT AGG UNDER MAG COAT

  • General Observation - MAG COAT 80% START

    19 ft. - General Observation - MAG COAT 80% START

  • Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - MODERATE AGG SPORATIC

    24.4 ft. - Surface Aggregate Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - MODERATE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    42.7 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

    69.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    108.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 70% START

    225.5 ft. - General Observation - MAG COAT 70% START

Observations (25)

DistanceCodeObservation
2SSSFLAKING CONCRETE
328.1SAVSEVERE AGG SPORATIC
328.1MGOMAG COAT 70% FINISH
2MGOMAG COAT 30% START 8:00 TO 4:00
7TFCCapped
8SAVMODERATE AGG SPORATIC
69.3SAVMODERATE AGG SPORATIC
328.1SAVMADERATE AGG SPORATIC
0AMH2:10AM
19MGOMAG COAT 80% START
328.6AMH2:40AM
319.9TFOpen
225.5MGOMAG COAT 70% START
42.7SAVSLIGHT AGG
42.7SAVSLIGHT AGG
42.7SAVSEVERE AGG SPORATIC
90.9TFOpen
8SAVSLIGHT AGG UNDER MAG COAT
0MWL
0MWM
24.4SAVMODERATE AGG SPORATIC
69.3SAVMODERATE AGG SPORATIC
328.1SSSFLAKING CONCRETE
69.3SAV
108.3SAVSEVERE AGG SPORATIC

Properties (6)

custom_field_three
SEVERE AGG SPORATIC
custom_field_two
2
customer
LACSD
datetime
2018-03-28T02:07:07-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false