- Date
- 03/27/2018
- W/O
- 0674248
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00495
- PipeID
- P06747
- Time
- 12:43 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0790
- Sewer Name
- 05 NORTH TORRANCE TRUNK
- City
- TORRANCE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 26
- Purpose
- Routine Assessment
- Project
- 20180327MDM_NORTH_TORRANCE_TRUNK
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 05 1525
- Downstream MH
- 05 1557
- Dir. of Survey
- Downstream
- Length Surveyed
- 220.7 ft.
- Total Length
- 220.7 ft.
- Structural Index
- 2
- Structural Quick
- 3122
- Structural Rating
- 7
- O&M Index
- 5
- O&M Quick
- 5100
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole 05 1525 to 05 1557 Observation photos (7)

2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Change - SEVERE AGG SPORATIC

2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

10.2 ft. - General Observation - 24" RCP

32.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

92.4 ft. - General Observation - MAG COAT 30%

119.7 ft. - General Observation - SLIME COAT ON PIPE

186.9 ft. - Water Level, 50 %of cross sectional area - MAG COAT 60%