Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2018, 07:27 AM
  • B 0360_B 0359 _26062018_003711.mp4

Date
06/26/2018
W/O
712401
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00091
PipeID
P08872
Time
12:27 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5705
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_712401_TV15051_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
B 0360
Downstream MH
B 0359
Dir. of Survey
Downstream
Length Surveyed
266.1 ft.
Total Length
266.1 ft.
Structural Index
3
Structural Quick
3K2H
Structural Rating
269
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
269
Pipe schematic from manhole B 0360 to B 0359
MH: B 0360MH: B 0359downstream0 ft. MGO - General Observation - ABANDONED MH0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 03600 ft. MWL - Water Level, 25 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.1 ft. AMH - Downstream Manhole, Survey Ends - B 0359266.1 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH266.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish266.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    35.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
35.4SSS
266.1AMHB 0359
0MGOABANDONED MH
266.1MGOCAPPED LATERAL 3 O'CLOCK @ MH
0MWM
35.4SAV
2.3SAV
266.1SAP
0AMHB 0360
266.1SSS
0MWL
7.8SAP

Properties (6)

additional_info
SC359663
custom_field_two
3
customer
LACSD
datetime
2018-06-26T00:27:29-07:00
documentation
PROPIPE
is_lateral_inspection
false