Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2018, 10:54 AM
  • 32 0041A_32 0041 _28062018_040152.mp4

Date
06/28/2018
W/O
712244
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P19806
Time
3:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5753
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
02
Purpose
Routine Assessment
Project
WO_712244_TV32012_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0041A
Downstream MH
32 0041
Dir. of Survey
Downstream
Length Surveyed
133.5 ft.
Total Length
133.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
52
Overall Index
2
Overall Quick
Overall Rating
52
Pipe schematic from manhole 32 0041A to 32 0041
MH: 32 0041AMH: 32 0041downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 32 0041A0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start133.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish133.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0041

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2DAGS
0MWL
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH32 0041A
0MWM
133.5DAGS
133.5AMH32 0041

Properties (7)

additional_info
SC359719
custom_field_two
4
customer
LACSD
datetime
2018-06-28T03:54:18-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27282