Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2018, 05:57 AM
  • 32 0060A_32 0060 _26062018_231236.mp4

Date
06/26/2018
W/O
712244
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P19825
Time
10:57 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5752
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
01
Purpose
Routine Assessment
Project
WO_712244_TV32012_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0060A
Downstream MH
32 0060
Dir. of Survey
Downstream
Length Surveyed
332.5 ft.
Total Length
332.5 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
143
Pipe schematic from manhole 32 0060A to 32 0060
MH: 32 0060AMH: 32 0060downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 32 0060A0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start118.9 ft. FS - Fracture Spiral, from 04 to 06 o'clock, within 8 inches of joint: YES125.1 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES270.2 ft. FS - Fracture Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES326 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES332.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish332.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0060

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 04 to 06 o'clock, within 8 inches of joint: YES

    118.9 ft. - Fracture Spiral, from 04 to 06 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    125.1 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    270.2 ft. - Fracture Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    326 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH32 0060A
332.5DAGS
270.2FS
118.9FS
2DAGS
326CM
332.5AMH32 0060
0MWM
0MWL
125.1CS

Properties (7)

additional_info
SC359718
custom_field_two
3
customer
LACSD
datetime
2018-06-26T22:57:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27282