Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2018, 05:08 AM
  • 32 0023_32 0022 _05072018_223632.mp4

Date
07/05/2018
W/O
712244
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P19787
Time
10:08 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5859
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
03
Purpose
Routine Assessment
Project
WO_712244_TV32012_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0023
Downstream MH
32 0022
Dir. of Survey
Downstream
Length Surveyed
370 ft.
Total Length
370 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
148
Pipe schematic from manhole 32 0023 to 32 0022
MH: 32 0023MH: 32 0022downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 00230 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start38.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"93.9 ft. MWL - Water Level, 50 %of cross sectional area109.5 ft. MWL - Water Level, 30 %of cross sectional area239.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"370 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish370 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK370 ft. AMH - Downstream Manhole, Survey Ends - 32 0022

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
370DAGS
93.9MWL
0AMH32 0023
2DAGS
38.2TF
109.5MWL
239.4TBA
370MGOCAPPED CONNECTION AT MH 3 O'CLOCK
0MWL
0MWM
370AMH32 0022

Properties (6)

additional_info
SC359726
custom_field_two
4
customer
LACSD
datetime
2018-07-05T22:08:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false