Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 3, 2018, 08:07 AM
  • 32 0026A_32 0026_03072018_011856.mp4

Date
07/03/2018
W/O
712244
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P19791
Time
1:07 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5857
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
03
Purpose
Routine Assessment
Project
WO_712244_TV32012_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0026A
Downstream MH
32 0026
Dir. of Survey
Downstream
Length Surveyed
146.9 ft.
Total Length
146.9 ft.
Structural Index
1
Structural Quick
1100
Structural Rating
1
O&M Index
2
O&M Quick
412E
O&M Rating
62
Overall Index
2
Overall Quick
Overall Rating
63
Pipe schematic from manhole 32 0026A to 32 0026
MH: 32 0026AMH: 32 0026downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 0026A2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start141.3 ft. CC - Crack Circumferential, from 12 to 12 o'clock, within 8 inches of joint: NO144.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish146.9 ft. AMH - Downstream Manhole, Survey Ends - 32 0026, RUN LIST STATES MH AT 202,.

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 12 to 12 o'clock, within 8 inches of joint: NO

    141.3 ft. - Crack Circumferential, from 12 to 12 o'clock, within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
0MWL
141.3CC
2DAGS
144.6DAGS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWM
0AMH32 0026A
146.9AMH32 0026, RUN LIST STATES MH AT 202,.

Properties (6)

additional_info
SC359724
custom_field_two
3
customer
LACSD
datetime
2018-07-03T01:07:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false