- Date
- 06/27/2018
- W/O
- 711900
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00700
- PipeID
- P14778
- Time
- 11:34 PM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5758
- Sewer Name
- 18 SCOTT AVENUE TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- WO_711900_TV18047_JUL2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 10 in.
- Width
- 10 in.
- Upstream MH
- 18 0930
- Downstream MH
- 18 0929
- Dir. of Survey
- Downstream
- Length Surveyed
- 343.8 ft.
- Total Length
- 343.8 ft.
- Structural Index
- 3
- Structural Quick
- 3L00
- Structural Rating
- 201
- O&M Index
- 3
- O&M Quick
- 3121
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 206
Pipe schematic from manhole 18 0930 to 18 0929 Observation photos (3)

8.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

277.9 ft. - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

343.8 ft. - Downstream Manhole, Survey Ends - 18 0929 ZOOMED IN