- Date
- 07/13/2018
- W/O
- 0716531
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00138
- PipeID
- P09801
- Time
- 3:41 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0933
- Sewer Name
- C JOINT OUTFALL C - UNIT 7B
- City
- HAWAIIAN GARDENS
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 19
- Page No.
- 08
- Purpose
- Capital Improvement Program Assesment
- Project
- 20180713MDM_JOINT_OUTFALL_C_UNIT_7B
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 33 in.
- Upstream MH
- C 0337
- Downstream MH
- C 0338
- Dir. of Survey
- Upstream
- Length Surveyed
- 270.8 ft.
- Total Length
- 270.8 ft.
- Structural Index
- 3
- Structural Quick
- 3121
- Structural Rating
- 5
- O&M Index
- 3
- O&M Quick
- 3121
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 10
Pipe schematic from manhole C 0337 to C 0338 Observation photos (6)

2 ft. - General Observation - MAG COAT 99% START 9:00 TO 3:00

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

20.1 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG

203.4 ft. - General Observation - ZOOM6 67'

203.4 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - BRICKS

270.4 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - ROCKS